Rectangular TDC ducts

Rectangular ducts with an integral sheet-metal flange.

Rectangular TDC ductsView photos

Assemble the TDC joint in 3D

Rotate the model to see both silicone applications, highlighted in blue.

3D model of two rectangular ducts. Drag or use the arrow keys to rotate. Use the zoom controls to move closer or farther away.

Assembly sequence

0 / 7
Exploded view

The two sections are separated. Select a step or play the animation to follow the assembly.

Illustrative model. Refer to the project drawings for clip quantity and position, fastener tightening requirements, and gasket and silicone specifications.

Rectangular duct, TDC connection

Rectangular ducts carry air through the system. With TDC construction, the sheet edges are formed into the flange that connects one section to the next. The duct body, connections, reinforcement and sealing must be specified together.

This construction can serve air-conditioning, ventilation and exhaust systems where it meets the project requirements. Air containing grease or contaminants, and special temperature conditions, require a specific assessment of the construction.

Materials and supply specifications

Materials: what to specify
MaterialRequired information
Galvanized steelNominal thickness, sheet specification and zinc coating.
Carbon steelSteel grade, thickness and specified surface protection.
Stainless steelAlloy, thickness and finish required for the application.
AluminumAlloy, temper, thickness and compatibility with the selected construction.

Straight sections, elbows, branches, reducers and transitions make up the system. Send dimensions and identification for each item; section lengths, finishes and supply conditions are defined in the quotation.

Thickness and mass by material

State the nominal thickness in millimeters. A commercial designation such as “#18” must be accompanied by the material and the supplier’s corresponding thickness; the gauge alone does not define the specification.

Theoretical mass by material (kg/m²), excluding coatings
Thickness (mm)Carbon steel304 stainless steel316 stainless steel3003 aluminum
0.433.383.403.441.17
0.503.933.954.001.37
0.655.105.145.201.77
0.806.286.326.402.18
0.957.467.517.602.59
1.007.857.908.002.73
1.118.718.778.883.03
1.259.819.8810.003.41
1.5512.1712.2512.404.23
1.9515.3115.4115.605.32
Mass depends on the material and alloyMass (kg/m²) = thickness (mm) × density (kg/m³) ÷ 1,000

Reference densities used: carbon steel 7,850; 304 stainless steel 7,900; 316 stainless steel 8,000; EN AW 3003 aluminum 2,730 kg/m³. Other alloys may have different values. Results are rounded to two decimal places.

Galvanized steel: include the coating

Calculate the base steel mass and add the zinc coating mass on both faces: base steel thickness (mm) × 7.85 + total coating mass (g/m²) ÷ 1,000. Confirm whether the stated thickness includes the coating to avoid counting it twice. A zinc coating designation identifies a coating class, not an exact mass for every sheet.

The thicknesses are calculation examples, not a stock list or manufacturing capacity schedule. Values exclude waste, flanges, reinforcement, accessories and other coatings. Finished mass must account for item geometry, alloy and supplied material tolerances.

Dimensions, pressure and reinforcement

Select sheet thickness together with the panel dimension, design pressure and reinforcement arrangement. Matching the largest duct dimension to a gauge without identifying the remaining conditions is insufficient.

Inputs to evaluate together
CriterionProject definition
GeometryWidth × height, section length and fitting geometry.
PressureValue in Pa, positive or negative sign and intended operating conditions.
SheetMaterial, nominal thickness and supply tolerances.
ReinforcementType, position, spacing and ties required by the construction detail.
JointsTransverse joint profile, longitudinal seam, fasteners and sealing.
InstallationSupports, assembly and maintenance access, insulation and obstructions.
Reference: ABNT NBR 16401-1:2024

The construction tables below use Annex B: galvanized sheet ducts for comfort air-conditioning, pressure classes 125, 250 and 500 Pa, with the longest side up to 1,800 mm. For stainless steel, aluminum, non-galvanized carbon steel, larger dimensions or other classes, clause 11.1.1 and Annex B.1 refer to the applicable SMACNA manual. The mass-by-material table serves a different purpose from construction selection.

“The pressure class of each duct section must be indicated on the project drawing.”

ABNT NBR 16401-1:2024 · clause 10.4.1.3 · informative translation
View pressure classes and velocity limits
Pressure classes — reference from Table 1
Class (Pa)Pressure typeMaximum velocity (m/s)
125Positive and negative10
250Positive and negative12.5
500Positive and negative12.5
750Positive and negative20
1000Positive20
1500PositiveAs specified
2500PositiveAs specified

The class represents the maximum internal static pressure expected, including occasional overpressure during normal operation. This general list is not a TDC product rating. Annex B provides construction arrangements for 125, 250 and 500 Pa. Source: clauses 10.4.1.1–10.4.1.3 and Table 1, pp. 25–26.

Original TDC construction tables

View the original table for each pressure class. Scroll to see the continuation or open the enlarged view.

Table B.7 · ±125 Pa
Table B.7 · ±125 Pa · Part 1/2 · p. 64
Table B.7 · ±125 Pa · Part 1/2 · p. 64 — Original captures in Portuguese.
Table B.7 · ±125 Pa · Part 2/2 · p. 65
Table B.7 · ±125 Pa · Part 2/2 · p. 65 — Original captures in Portuguese.
Table B.8 · ±250 Pa
Table B.8 · ±250 Pa · Part 1/2 · p. 65
Table B.8 · ±250 Pa · Part 1/2 · p. 65 — Original captures in Portuguese.
Table B.8 · ±250 Pa · Part 2/2 · p. 66
Table B.8 · ±250 Pa · Part 2/2 · p. 66 — Original captures in Portuguese.
Table B.9 · ±500 Pa
Table B.9 · ±500 Pa · Part 1/2 · p. 66
Table B.9 · ±500 Pa · Part 1/2 · p. 66 — Original captures in Portuguese.
Table B.9 · ±500 Pa · Part 2/2 · p. 67
Table B.9 · ±500 Pa · Part 2/2 · p. 67 — Original captures in Portuguese.
Table 1 · Pressure classes
Table 1 · Pressure classes · Part 1/1 · p. 26
Table 1 · Pressure classes · Part 1/1 · p. 26 — Original captures in Portuguese.

Original captures in Portuguese. The supplied PDF shows the interval “491 a 450”; verify this range before sizing ductwork.

Source: ABNT NBR 16401-1:2024. © ABNT 2024 — All rights reserved.

Standard tables

100%

Original captures in Portuguese.

Source: ABNT NBR 16401-1:2024. © ABNT 2024 — All rights reserved.

Additional reference: selected examples for joints at 1.20 m

Galvanized TDC construction examples

Selected condition: joints at 1.20 m, from the 1.20 m sheet or coil columns of Tables B.7, B.8 and B.9, without the intermediate-reinforcement option. Each cell shows wall thickness and joint reinforcement. These are individual reference dimensions; other sizes and arrangements require the complete tables.

Wall thickness (mm) and joint reinforcement · joints at 1.20 m
Reference dimension (mm)±125 Pa · B.7±250 Pa · B.8±500 Pa · B.9
6500.55 mm · N/R0.55 mm · N/R0.55 mm · N/R
7500.55 mm · N/R0.55 mm · N/R0.70 mm · N/R
9000.55 mm · N/R0.55 mm · N/R0.70 mm · N/R
10000.55 mm · N/R0.70 mm · N/R0.85 mm · N/R
12000.55 mm · N/R0.70 mm · N/R0.85 mm · TRjt or (2C)
13000.70 mm · N/R0.85 mm · N/R1.00 mm · TRjt or (2E)
15000.70 mm · N/R0.85 mm · N/R1.00 mm · TRjt or (2E)
18000.85 mm · N/R0.85 mm · TRjt or (2E)1.00 mm · TRjt or (2H)

Reading the table: N/R means joint reinforcement is not required for that combination; it does not eliminate the need for corner pieces, clips, fasteners, sealing or supports. TRjt denotes a tie rod fixed at the center of the joint on each side, 25 mm from the joint. Alternatives (2C), (2E) and (2H) retain the standard’s codes: their detail and stiffness must be specified according to Annex B; they are not sheet gauges.

The largest dimension determines the thickness of all four sides. Joints and reinforcement must also be checked for the shorter side. The installer selects the construction combination in accordance with the project. Source: clause B.2.2; Tables B.1, B.2 and B.7–B.9, pp. 58–67. This excerpt is not a stock list, declared product capability or certification.

Beads, reinforcement and supports have different roles

Cross-breaks and beads are formed features of the panels. Intermediate reinforcement and tie elements must follow the selected construction detail. Supports carry the duct system and must account for the installed components. These features are not automatically interchangeable.

35 mm TDC

The 35 mm dimension is the nominal height of the flange profile. It is not the sheet thickness and does not establish a pressure class on its own.

Seams and connection components

Identifying each joint
ElementLocation and function
Longitudinal seamCloses the duct body along the section.
Transverse TDC jointConnects the ends of two sections using the flange formed in the sheet.
Separate flangeA profile attached to the duct; a different connection solution that requires a separate specification.

Specify whether the longitudinal seam is mechanically locked or welded, as required by the selected construction. “TDC” describes the transverse connection; it does not, by itself, identify how the duct body is closed.

TDC assembly components
ComponentWhat to check
Formed flangeProfile height, geometry, alignment and sheet integrity.
TDC flange corner pieceCompatibility with the profile and specified fastening.
TDC clipType, fit, quantity and distribution according to the assembly detail.
Bolts and nutsSpecified dimensions, material and tightening conditions.
Gasket tape or sealantCompatibility, application and sealing continuity, including at corners.

Figure B.3 (p. 68) shows a typical TDC flange joint, with corner pieces, clips and fasteners, and continuous sealing along the flanges and around the corners. Component dimensions and distribution must match the construction detail adopted for the project.

Clip quantities and positions must follow the applicable connection detail. See the application material under Manuals and drawings.

Sealing, insulation and inspection

  1. Before joining: check item identification, dimensions, flange condition and cleanliness of the mating surfaces.
  2. At the connection: apply the specified sealing, align the sections and install corner pieces, fasteners and clips according to the drawing and component instructions.
  3. At system handover: inspect supports, access points, joints and insulation continuity. When the project requires leakage testing, record the test section, test pressure and acceptance criterion.

Sealing and airtightness

Sealing must achieve the specified leakage class CL. Branches, equipment connections, dampers, terminals and access covers receive the same sealing treatment as the ducts. Sealant selection must consider durability, vibration and chemical compatibility with the sheet and the conditioned space. Reference: clauses 10.4.3.1–10.4.3.4.

Sealing and tests: design and assembly information
StageWhat to specify or checkReference
Acceptance criterionCL, allowable leakage and the portion of the system to test, specified by the designer in agreement with the client for the application.10.4.2.2–10.4.2.5
Test pressureRespect working-pressure and construction-class limits. Negative-pressure sections are tested with positive pressure.Table 2, note a; 10.4.5.6–10.4.5.7
Test timingTest during fabrication and installation, before joints are covered by insulation or become inaccessible.Annex D.2.1
Result recordIdentify the section, area, pressure, measured leakage and achieved class for comparison with the design CL.Annex D.2.2–D.2.3

The test pressure does not change the specified CL. Leakage and sampling percentages depend on the system and project agreement; one percentage does not apply to every installation. Annex D is informative and provides supporting guidance.

Thermal insulation

Define the material, thickness, finish and internal or external application. For cold-air systems, condensation control also depends on humidity, temperature and the continuity of the vapor barrier, where specified.

Manuals and drawings

Explore the flange joint in 3D and download the TDC clip application files.

The assembly also uses flange corner pieces, gasket tape and fasteners. Explore duct accessories →

What to send for a quotation

Information checklist for the quotation
InformationWhat to send
Project and revisionIdentified drawings, item list and valid revision for pricing.
Dimensions and quantitiesWidth × height × length, type and quantity of each item.
Material and constructionSheet material, thickness in mm, longitudinal seam type, flange and reinforcement.
System conditionsApplication, positive or negative pressure and design temperature.
Additional scopeInsulation, sealing, accessories, installation and testing included in the scope.
DeliveryProject location, areas or batches and required delivery date.
Standards and acceptance criteriaStandard and edition, pressure class by section, design CL and test plan.
Standards used in this guide

ABNT NBR 16401-1:2024 — Air conditioning installations — Central and unitary systems — Part 1: System design. References: clauses 10.4 and 11.1.1, Annex B (normative) and Annex D (informative). The tables on this page are selected references identified by clause, table and page; specifications must consider the complete standard and project details. English text is an informative translation. Referencing the standard does not automatically certify Top Dutos products.

Can I choose thickness based only on width?

No. Width is one construction input. Selection must also consider positive or negative pressure, section length and reinforcement spacing, material and joint arrangement.

Which technical references should be considered?

Identify the publication and edition adopted in the project specification. SMACNA has separate documents for HVAC ducts, industrial ducts and leakage testing. Applicable ABNT standards must also be identified for the installation. Referencing a standard does not automatically certify a product.

SMACNA technical publications ↗ · ABNT catalogue ↗

Basis of the mass table

Our calculation for 1 m² of sheet uses reference densities from the data sheets below. Carbon steel, stainless steel and aluminum do not share one factor; galvanized steel also requires separate accounting for its coating.

Carbon steel — SSAB ↗ · 304 stainless steel — Outokumpu ↗ · 316 stainless steel — Outokumpu ↗ · 3003 aluminum — Alumeco ↗ · Galvanized coating — SSAB ↗

Request your quote

Send drawings, the project location and the required delivery date.

Submit my project

Complete your solution

Bob, the Top Dutos mascotYour guide here

Your guide at Top Dutos

Ready for the next step in your project?

I'm Bob. I can help you find products, answer questions and prepare your quote request.

Direct WhatsApp contact (opens in a new tab)

I'm here in the right-hand corner whenever you need me.

Your guide at Top Dutos

Hi, I'm Bob!

Bob, the Top Dutos mascot

How would you like to continue? Choose one of the three options below.

Direct WhatsApp contactContact our team on WhatsApp(opens in a new tab)

Virtual assistant

Connecting you to Bob…