Rectangular ducts with an integral sheet-metal flange.
View photos →







Rotate the model to see both silicone applications, highlighted in blue.
The two sections are separated. Select a step or play the animation to follow the assembly.
Illustrative model. Refer to the project drawings for clip quantity and position, fastener tightening requirements, and gasket and silicone specifications.
01 · Product overview
Rectangular ducts carry air through the system. With TDC construction, the sheet edges are formed into the flange that connects one section to the next. The duct body, connections, reinforcement and sealing must be specified together.
This construction can serve air-conditioning, ventilation and exhaust systems where it meets the project requirements. Air containing grease or contaminants, and special temperature conditions, require a specific assessment of the construction.
| Material | Required information |
|---|---|
| Galvanized steel | Nominal thickness, sheet specification and zinc coating. |
| Carbon steel | Steel grade, thickness and specified surface protection. |
| Stainless steel | Alloy, thickness and finish required for the application. |
| Aluminum | Alloy, temper, thickness and compatibility with the selected construction. |
Straight sections, elbows, branches, reducers and transitions make up the system. Send dimensions and identification for each item; section lengths, finishes and supply conditions are defined in the quotation.
02 · Sheet reference
State the nominal thickness in millimeters. A commercial designation such as “#18” must be accompanied by the material and the supplier’s corresponding thickness; the gauge alone does not define the specification.
| Thickness (mm) | Carbon steel | 304 stainless steel | 316 stainless steel | 3003 aluminum |
|---|---|---|---|---|
| 0.43 | 3.38 | 3.40 | 3.44 | 1.17 |
| 0.50 | 3.93 | 3.95 | 4.00 | 1.37 |
| 0.65 | 5.10 | 5.14 | 5.20 | 1.77 |
| 0.80 | 6.28 | 6.32 | 6.40 | 2.18 |
| 0.95 | 7.46 | 7.51 | 7.60 | 2.59 |
| 1.00 | 7.85 | 7.90 | 8.00 | 2.73 |
| 1.11 | 8.71 | 8.77 | 8.88 | 3.03 |
| 1.25 | 9.81 | 9.88 | 10.00 | 3.41 |
| 1.55 | 12.17 | 12.25 | 12.40 | 4.23 |
| 1.95 | 15.31 | 15.41 | 15.60 | 5.32 |
Reference densities used: carbon steel 7,850; 304 stainless steel 7,900; 316 stainless steel 8,000; EN AW 3003 aluminum 2,730 kg/m³. Other alloys may have different values. Results are rounded to two decimal places.
Calculate the base steel mass and add the zinc coating mass on both faces: base steel thickness (mm) × 7.85 + total coating mass (g/m²) ÷ 1,000. Confirm whether the stated thickness includes the coating to avoid counting it twice. A zinc coating designation identifies a coating class, not an exact mass for every sheet.
The thicknesses are calculation examples, not a stock list or manufacturing capacity schedule. Values exclude waste, flanges, reinforcement, accessories and other coatings. Finished mass must account for item geometry, alloy and supplied material tolerances.
03 · Construction criteria
Select sheet thickness together with the panel dimension, design pressure and reinforcement arrangement. Matching the largest duct dimension to a gauge without identifying the remaining conditions is insufficient.
| Criterion | Project definition |
|---|---|
| Geometry | Width × height, section length and fitting geometry. |
| Pressure | Value in Pa, positive or negative sign and intended operating conditions. |
| Sheet | Material, nominal thickness and supply tolerances. |
| Reinforcement | Type, position, spacing and ties required by the construction detail. |
| Joints | Transverse joint profile, longitudinal seam, fasteners and sealing. |
| Installation | Supports, assembly and maintenance access, insulation and obstructions. |
The construction tables below use Annex B: galvanized sheet ducts for comfort air-conditioning, pressure classes 125, 250 and 500 Pa, with the longest side up to 1,800 mm. For stainless steel, aluminum, non-galvanized carbon steel, larger dimensions or other classes, clause 11.1.1 and Annex B.1 refer to the applicable SMACNA manual. The mass-by-material table serves a different purpose from construction selection.
“The pressure class of each duct section must be indicated on the project drawing.”
| Class (Pa) | Pressure type | Maximum velocity (m/s) |
|---|---|---|
| 125 | Positive and negative | 10 |
| 250 | Positive and negative | 12.5 |
| 500 | Positive and negative | 12.5 |
| 750 | Positive and negative | 20 |
| 1000 | Positive | 20 |
| 1500 | Positive | As specified |
| 2500 | Positive | As specified |
The class represents the maximum internal static pressure expected, including occasional overpressure during normal operation. This general list is not a TDC product rating. Annex B provides construction arrangements for 125, 250 and 500 Pa. Source: clauses 10.4.1.1–10.4.1.3 and Table 1, pp. 25–26.
View the original table for each pressure class. Scroll to see the continuation or open the enlarged view.






Original captures in Portuguese. The supplied PDF shows the interval “491 a 450”; verify this range before sizing ductwork.
Source: ABNT NBR 16401-1:2024. © ABNT 2024 — All rights reserved.
Selected condition: joints at 1.20 m, from the 1.20 m sheet or coil columns of Tables B.7, B.8 and B.9, without the intermediate-reinforcement option. Each cell shows wall thickness and joint reinforcement. These are individual reference dimensions; other sizes and arrangements require the complete tables.
| Reference dimension (mm) | ±125 Pa · B.7 | ±250 Pa · B.8 | ±500 Pa · B.9 |
|---|---|---|---|
| 650 | 0.55 mm · N/R | 0.55 mm · N/R | 0.55 mm · N/R |
| 750 | 0.55 mm · N/R | 0.55 mm · N/R | 0.70 mm · N/R |
| 900 | 0.55 mm · N/R | 0.55 mm · N/R | 0.70 mm · N/R |
| 1000 | 0.55 mm · N/R | 0.70 mm · N/R | 0.85 mm · N/R |
| 1200 | 0.55 mm · N/R | 0.70 mm · N/R | 0.85 mm · TRjt or (2C) |
| 1300 | 0.70 mm · N/R | 0.85 mm · N/R | 1.00 mm · TRjt or (2E) |
| 1500 | 0.70 mm · N/R | 0.85 mm · N/R | 1.00 mm · TRjt or (2E) |
| 1800 | 0.85 mm · N/R | 0.85 mm · TRjt or (2E) | 1.00 mm · TRjt or (2H) |
Reading the table: N/R means joint reinforcement is not required for that combination; it does not eliminate the need for corner pieces, clips, fasteners, sealing or supports. TRjt denotes a tie rod fixed at the center of the joint on each side, 25 mm from the joint. Alternatives (2C), (2E) and (2H) retain the standard’s codes: their detail and stiffness must be specified according to Annex B; they are not sheet gauges.
The largest dimension determines the thickness of all four sides. Joints and reinforcement must also be checked for the shorter side. The installer selects the construction combination in accordance with the project. Source: clause B.2.2; Tables B.1, B.2 and B.7–B.9, pp. 58–67. This excerpt is not a stock list, declared product capability or certification.
Cross-breaks and beads are formed features of the panels. Intermediate reinforcement and tie elements must follow the selected construction detail. Supports carry the duct system and must account for the installed components. These features are not automatically interchangeable.
The 35 mm dimension is the nominal height of the flange profile. It is not the sheet thickness and does not establish a pressure class on its own.
04 · Connection details
| Element | Location and function |
|---|---|
| Longitudinal seam | Closes the duct body along the section. |
| Transverse TDC joint | Connects the ends of two sections using the flange formed in the sheet. |
| Separate flange | A profile attached to the duct; a different connection solution that requires a separate specification. |
Specify whether the longitudinal seam is mechanically locked or welded, as required by the selected construction. “TDC” describes the transverse connection; it does not, by itself, identify how the duct body is closed.
| Component | What to check |
|---|---|
| Formed flange | Profile height, geometry, alignment and sheet integrity. |
| TDC flange corner piece | Compatibility with the profile and specified fastening. |
| TDC clip | Type, fit, quantity and distribution according to the assembly detail. |
| Bolts and nuts | Specified dimensions, material and tightening conditions. |
| Gasket tape or sealant | Compatibility, application and sealing continuity, including at corners. |
Figure B.3 (p. 68) shows a typical TDC flange joint, with corner pieces, clips and fasteners, and continuous sealing along the flanges and around the corners. Component dimensions and distribution must match the construction detail adopted for the project.
Clip quantities and positions must follow the applicable connection detail. See the application material under Manuals and drawings.
05 · Preparation and assembly
Sealing must achieve the specified leakage class CL. Branches, equipment connections, dampers, terminals and access covers receive the same sealing treatment as the ducts. Sealant selection must consider durability, vibration and chemical compatibility with the sheet and the conditioned space. Reference: clauses 10.4.3.1–10.4.3.4.
| Stage | What to specify or check | Reference |
|---|---|---|
| Acceptance criterion | CL, allowable leakage and the portion of the system to test, specified by the designer in agreement with the client for the application. | 10.4.2.2–10.4.2.5 |
| Test pressure | Respect working-pressure and construction-class limits. Negative-pressure sections are tested with positive pressure. | Table 2, note a; 10.4.5.6–10.4.5.7 |
| Test timing | Test during fabrication and installation, before joints are covered by insulation or become inaccessible. | Annex D.2.1 |
| Result record | Identify the section, area, pressure, measured leakage and achieved class for comparison with the design CL. | Annex D.2.2–D.2.3 |
The test pressure does not change the specified CL. Leakage and sampling percentages depend on the system and project agreement; one percentage does not apply to every installation. Annex D is informative and provides supporting guidance.
Define the material, thickness, finish and internal or external application. For cold-air systems, condensation control also depends on humidity, temperature and the continuity of the vapor barrier, where specified.
06 · Technical files
Explore the flange joint in 3D and download the TDC clip application files.
The assembly also uses flange corner pieces, gasket tape and fasteners. Explore duct accessories →
07 · Prepare your quote request
| Information | What to send |
|---|---|
| Project and revision | Identified drawings, item list and valid revision for pricing. |
| Dimensions and quantities | Width × height × length, type and quantity of each item. |
| Material and construction | Sheet material, thickness in mm, longitudinal seam type, flange and reinforcement. |
| System conditions | Application, positive or negative pressure and design temperature. |
| Additional scope | Insulation, sealing, accessories, installation and testing included in the scope. |
| Delivery | Project location, areas or batches and required delivery date. |
| Standards and acceptance criteria | Standard and edition, pressure class by section, design CL and test plan. |
ABNT NBR 16401-1:2024 — Air conditioning installations — Central and unitary systems — Part 1: System design. References: clauses 10.4 and 11.1.1, Annex B (normative) and Annex D (informative). The tables on this page are selected references identified by clause, table and page; specifications must consider the complete standard and project details. English text is an informative translation. Referencing the standard does not automatically certify Top Dutos products.
No. Width is one construction input. Selection must also consider positive or negative pressure, section length and reinforcement spacing, material and joint arrangement.
Identify the publication and edition adopted in the project specification. SMACNA has separate documents for HVAC ducts, industrial ducts and leakage testing. Applicable ABNT standards must also be identified for the installation. Referencing a standard does not automatically certify a product.
Our calculation for 1 m² of sheet uses reference densities from the data sheets below. Carbon steel, stainless steel and aluminum do not share one factor; galvanized steel also requires separate accounting for its coating.
Carbon steel — SSAB ↗ · 304 stainless steel — Outokumpu ↗ · 316 stainless steel — Outokumpu ↗ · 3003 aluminum — Alumeco ↗ · Galvanized coating — SSAB ↗
Send drawings, the project location and the required delivery date.

Ducts with separate flanges, such as angle iron or flat bar.
Explore the range →
Welded-seam ducts in aluminum, galvanized steel, stainless steel or carbon steel.
Explore the range →
Flange corner pieces, clips, gaskets, sealing tape and fasteners for duct assembly.
Explore the range →